My biggest problem with batteries for grid outages is that the only outages I am actually concerned with would drain them to zero before the outage is resolved. For short term, smaller/portable batteries are fantastic at bridging a few hours. Plug the wifi & fridge in and you can sometimes go for 2-3 days.

I am not aware of any economically feasible way to run my 5+ ton HVAC system full-time on batteries after a hurricane just reset all the infrastructure, and you do need to run it full time because of the insane humidity and latent heat that follows a tropical system. Doing the math, I'd need something approaching 800kWh of storage to ride through this kind of event (7+ days). This is approaching half a million dollars in batteries. I can install an extremely nice 1800 RPM generator for ~15% of this cost, which would also include a year's worth of propane buried on the property.

I think a simple generator on an ATS remains undefeated from an engineering perspective. If you have an air cooled unit, the maintenance is not much more complicated than with a lawnmower. You just have one extra spark plug to deal with, and sometimes the oil pressure sensor needs replacing. I can get my stubborn Honda generator to start with all kinds of weird tricks. If my Ecoflow battery starts to act weird, I have very little recourse by comparison.