Comment

Comment by shdudns

How is DC better than a three phase delta 800Vrms, at 400Hz?

- Three conductors vs two, but they can be the next gauge up since the current flows on three conductors

- no significant skin effect at 400Hz -> use speaker wire, lol.

- large voltage/current DC brakers are.. gnarly, and expensive. DC does not like to stop flowing

- The 400Hz distribution industry is massive; the entire aerospace industry runs on it. No need for niche or custom parts.

- 3 phase @ 400Hz is x6 = 2.4kHz. Six diodes will rectify it with almost no relevant amount of ripple (Vmin is 87% of Vmax) and very small caps will smooth it.

As an aside, with three (or more) phase you can use multi-tap transformers and get an arbitrary number of poles. 7 phases at 400Hz -> 5.6kHz. Your PSU is now 14 diodes and a ceramic cap.

- you still get to use step up/down transformers, but at 400Hz they're very small.

- merging power sources is a lot easier (but for the phase angle)

- DC-DC converters are great, but you're not going to beat a transformer in efficiency or reliability

parent shdudns 7 months ago