Comment by millebe

NEC chapter 7, article 720 covers wiring of less than 50V. It's important to note that elsewhere in the NEC and other codes, "low voltage" is defined as <600V, <1000V, or <2000V, depending on the code and code cycle.

Your fire marshal might have passed 5V cabling duct taped to a wall, but it would be in violation of 720.11:

    720.11 Mechanical Execution of Work
    Circuits operating at less than 50 volts shall be installed in a neat and workmanlike manner. Cables shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use.