Yes, you cannot reasonably run these high-power devices on low-voltage DC (12-48V), this is also said in the article. But the reason is not that these devices cannot run on DC in principle, the problem is cable loss. For running devices which need >1kW on low-voltage DC, we are talking at least 20-80A, depending on the voltage. So you need thick cables, which are expensive and hard to deal with (amount of space needed, securing connections, avoiding bending, everything becomes problematic with these cables). Any little mistake done with cabling is immediately a fire hazard.
So in the end, the article says: say good bye to your washing machine, dish washer, electric kettle, electric stove, etc. I mean, the site is called "low tech magazine" for a reason...