Check the actual papers.[1][2] For single-phase meters, which covers most residential uses, this is a non-problem: "No deviation beyond the specification could be observed; no influence of interference due to interfering or distorted voltage, and no influence caused by interfering currents were observed." All the problems were seen with 3-phase meters, usually found only in industrial and commercial environments.

Figure 3 of [1] is puzzling. They claim to be testing a 3-phase meter, but the circuit shown is single-phase. Are they testing 3-phase meters with only one phase connected? That's way out of balance; 3-phase systems normally have at least roughly equal loads on each phase. While a 3-phase meter with an wildly asymmetrical load ought to measure accurately, that's not a normal condition.

[1] http://doc.utwente.nl/102016/1/Runaway_energy_Meters.pdf [2] http://ieeexplore.ieee.org/document/7866234/